Industry ESS solution layout is flexible and changeable.
High-life lithium iron phosphate battery system, BMS management system, high-performance energy storage converter,
fire safety system, power distribution system and thermal management system are integrated into a standard outdoor cabinet.

| Product model | ES100-2 | ES185-2 |
| Battery system parameters | ||
| Cell specification | LFP 280Ah | LFP 280Ah |
| Battery rated energy | 236.5kWh | 372.7kWh |
| Battery temperature control mode | Air-cooled (industrial air conditioning) | water-cooled |
| AC system parameters | ||
| Rated power at AC side | 100kW | 185kW |
| Maximum power at AC side | 110kW | 220kW |
| Rated voltage at AC side | 400Vac | 690Vac |
| Access mode | Three-phase three-wire | Three-phase three-wire |
| Operating voltage range at AC side | 340~440V | 586-759V |
| Power factor | >0.99 | >0.99 |
| Adjustable range of power factor | -1~1 | -1~1 |
| Rated grid frequency | 50/60Hz | 50/60Hz |
| Grid frequency range | 45~55 Hz / 55~ 65 Hz | 45~55 Hz / 55~ 65 Hz |
| Maximum total harmonic distortion | < 3% ( rated power) | < 3% (rated power) |
| DC component | <0.5% | <0.5% |
| Cooling method | Forced air cooling | Forced air cooling |
| Isolation mode | None | None |
| Communication parameters | ||
| System communication interface (external) | RS485/Ethernet | RS485/Ethernet |
| System communication protocol (external) | MODBUS-RTU/MODBUS-TCP/IEC61850 | MODBUS-RTU/MODBUS-TCP/IEC61850 |
| System parameters | ||
| System efficiency | ≥90% | ≥91% |
| Charge and discharge rate | 0.5C | 0.5C |
| Depth of discharge | 95% | 95% |
| Number of cycles | 6000 | 6000 |
| Degree of protection | IP55 | IP55 |
| Operating temperature range | -30~50℃ | -30~50℃ |
| Operating humidity range | 0 ~ 95% RH non-condensing | 0 ~ 95% RH non-condensing |
| Operating altitude | 2000m | 2000m |
| Dimensions (W × D × H) | 1250×1200×2450mm | 1300×1300×2450mm |
| Equipment weight (including battery) | 2600kg | 3600kg |
| Fire protection system configuration | Combustible gas/fog/temperature detection + total flooding gas fire extinguishing (perfluorohexanone) + water fire extinguishing (reserved) | Combustible gas/fog/temperature detection + total flooding gas fire extinguishing (perfluorohexanone) + water fire extinguishing (reserved) |